UPS Model
Technology
On-Line Double Conversion transformerless (VFI-SS-111)
Audible noise
< 48 dBA a 1 m
Dimension (UPS) WxHxD
40x107x78 cm
Dimension (with packing) WxHxD
72,5x127,5x87,5 cm
Input
Nominal voltage
380Vac/400Vac/415Vac
Input voltage range ( F-N )
187Vac-280Vac to 100% load, 120Vac-280Vac to 64% load, 80Vac-280Vac to 42% load
Nominal frequency
50/60 Hz
Input frequency range On-Line mode
±10%
Input current harmonic distortion (THDi)
≤4%
Output
Nominal voltage
380Vac/400Vac/415Vac
Voltage Regulation at %100 linear load (On-Line and Battery mode)
±1%
Voltage THD at rated linear load
<3% (linear load)
Frequency stability
±0,1 Hz
Inverter waveform
Sinewave
Overload capability
125% for 10 minutes - 150% for 1 minute
Efficiency
>94% (On-Line mode), >92% (Battery mode), >99% (ECO mode)
Transfer time
0 ms (On-Line)
Output connections
Terminal block
Bypass
Nominal voltage (F-N)
220Vac/230Vac/240Vac
Eco Mode
Input frequency range
± 5%
Battery
Type
Lead acid, sealed, maintenance free
Batteries number
62 (2x31 - Installed inside)
Battery charge time (typical)
6-8 hours
Nominal voltage
372Vdc + 372Vdc
Extended autonomy
External Battery Box (optional)
Interfacing
Interface (comunication port)
RS232 and RS422
Dry contact interface
Power failure, low battery, Bypass mode,no output power
Generator adaptability
Yes
Software
Generex UPS Management (Compatible with WINDOWS, UNIX, LINUX, MAC OS X, SUN SOLARIS) - optional
SNMP interface
SNMP Generex internal module CS121BSC model - optional
Parallel configuration
Parallel Interface
Yes (optional)
Redundant parallel system
up to 4 units
Environmental specification
Storage temperature
From -15 to 40 °C (for UPS with battery inside, see “Storage of batteries in UPS and Battery Box” graphic)
Working temperature
From 0 to 40 °C (recommended from 20 to 25 °C, for longer battery life see “Battery life in service” graphic)
Humidity
< 95% without condensation
Certifications
CE (standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classification IEC EN 62040-3)
Warranty
UPS 3-P/3-P, POWER 15 KVA, WITH ISOLATION TRANSFORMER, ONLINE DOUBLE CONVERSION TECNOLOGY WITHOUT TRANSFORMER, DSP(DIGITAL SIGNAL PROCESSOR) SYSTEM, MULTIFUNCTION LCD DISPLAY, WITHOUT BATTERIES, DIMENSIONS 40X78X107 CM, WEIGHT 222 KG
STANDARD WARRANTY: 12 MONTHS ELECTRONIC PARTS