UPS Model
Technology
On-Line Double Conversion transformerless (VFI-SS-111)
Audible noise
< 52 dBA a 1 m
Dimension (UPS) WxHxD
40x107x78 cm
Dimension (with packing) WxHxD
72,5x127,5x87,5 cm
Input
Nominal voltage
380Vac/400Vac/415Vac
Input voltage range ( F-N )
187Vac-280Vac to 100% load, 120Vac-280Vac to 64% load, 80Vac-280Vac to 42% load
Nominal frequency
50/60 Hz
Input frequency range On-Line mode
±10%
Input current harmonic distortion (THDi)
≤4%
Output
Nominal voltage
380Vac/400Vac/415Vac
Voltage Regulation at %100 linear load (On-Line and Battery mode)
±1%
Voltage THD at rated linear load
<3% (linear load)
Frequency stability
±0,1 Hz
Inverter waveform
Sinewave
Overload capability
125% for 10 minutes - 150% for 1 minute
Efficiency
>94% (On-Line mode), >92% (Battery mode), >99% (ECO mode)
Transfer time
0 ms (On-Line)
Output connections
Terminal block
Bypass
Nominal voltage (F-N)
220Vac/230Vac/240Vac
Input frequency range
± 5%
Battery
Type
Lead acid, sealed, maintenance free
Batteries number
62 (2x31 - Installed inside)
Battery charge time (typical)
6-8 hours
Nominal voltage
372Vdc + 372Vdc
Extended autonomy
External Battery Box (optional)
Interfacing
Interface (comunication port)
RS232 and RS422
Dry contact interface
Power failure, low battery, Bypass mode,no output power
Generator adaptability
Yes
Software
Generex UPS Management (Compatible with WINDOWS, UNIX, LINUX, MAC OS X, SUN SOLARIS) - optional
SNMP interface
SNMP Generex internal module CS121BSC model - optional
Parallel configuration
Parallel Interface
Yes (optional)
Redundant parallel system
up to 4 units
Environmental specification
Storage temperature
From -15 to 40 °C (for UPS with battery inside, see “Storage of batteries in UPS and Battery Box” graphic)
Working temperature
From 0 to 40 °C (recommended from 20 to 25 °C, for longer battery life see “Battery life in service” graphic)
Humidity
< 95% without condensation
Certifications
CE (standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classification IEC EN 62040-3)
Warranty
Accessories
Bypass Box for Evo Dsp TT 10-30 KVA
FGCBYP30TT
Internal SNMP for Evo Dsp TM/TT
FGCNETAG6
Remote Panel for Evo Dsp TM/TT
FGCEVODSRP1
Remote Panel cable for Evo Dsp TM/TT 25m length
FGCEVODSCARP1
Upsman software Interfacing UPS + RCCMD Client for Client management + 1 license for RCCMD
FGCSWUMSU
RCCMD Client License
FGCSWUMMS
Separated Bypass input
On request
UPS with isolation transformer installed inside (in this configuration the UPS can’t contain batteries inside)
UPS Code + Final “I”
UPS configured for Parallel connection
UPS Code + Final “P”
UPS 3-P/SINGLE-PHASE, POWER 30 KVA, ONLINE DOUBLE CONVERSION TECNOLOGY WITHOUT TRANSFORMER, DSP(DIGITAL SIGNAL PROCESSOR) SYSTEM, MULTIFUNCTION LCD DISPLAY, WITHOUT BATTERIES, PREPARED FOR 62 BATTERIES 7.2-9-11AH, DIMENSIONS 40X78X107 CM, WEIGHT 100 KG
STANDARD WARRANTY: 12 MONTHS ELECTRONIC PARTS