UPS Model
Technology
On-Line Double Conversion transformerless (VFI-SS-111)
Audible noise
< 45 dBA a 1 m
Positioning
Into 19’’ rack (3U), or tower positioning
Dimension(UPS) WxHxD
44X13X48 cm
Dimension (with packing) WxHxD
60,5x31x65,5 cm
Equipped with
1 power cable, 2 output cables (IEC type), Upsilon 2000 software, RS232 cable, connector IEC type 320 C20 to be wired for power output, 2 plastic pedestals for Tower positioning, 2 metal handle for 19’’ Rack mounting
Input
Nominal voltage
Single-phase 230Vac
Input voltage range
+20%/-25%
Nominal frequency
50/60 Hz
Input frequency range On-Line mode
+/- 5%
Output
Voltage
Single-phase 230Vac
Voltage Regulation at %100 linear load (On-Line and Battery mode)
±2%
Voltage THD at rated linear load
<3% (linear load), <6% (non-linear load)
Frequency stability
±0,2 Hz
Inverter waveform
Sinewave
Overload capability
<150% for 30 sec, >150% for 10 cycles
Efficiency
>92% (Line/Battery mode)
Transfer time
0 ms (On-Line)
Outlets
6 (IEC 320 C13 type) + 1 (IEC 320 C19 type)
Bypass
Battery
Type
Lead acid, sealed, maintenance free
Batteries number
8 (internal)
Battery charge time (typical)
6-8 hours
Nominal battery voltage
96Vdc
Battery specification
12Vdc - 7,2Ah (specific dimensions for this product)
Backup time (typical)
16 min
Extended autonomy
External Battery Box (optional)
Interfacing
Interface (communication ports)
RS232
Interface with free contact
Yes (optional)
Software
UPSILON 2000 (compatible with OS WINDOWS, UNIX, LINUX, ecc.)
SNMP interface
SNMP internal module (compatible with WINDOWS, UNIX, LINUX, ecc.) - optional
Phone/modem line protection
RJ11/RJ45 plug
Environmental specification
Storage temperature
From -15 to 40 °C (for Battery Box with battery inside, see “Storage of batteries in UPS and Battery Box” graphic)
Working temperature
From 0 to 40 °C (recommended from 20 to 25 °C, for a correct battery use see “Battery life in service” graphic)
Humidity
< 95% without condensation
Certifications
CE (Standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classification IEC EN 62040-3)
Warranty
Accessories
Bypass Box for UPS MM from 1 KVA to 3,6 KVA
FGCBYPIEC
Dry Contact for Evo from 1 to 3 KVA
FGCEVODRY1
Internal SNMP from single-phase UPS
FGCNETAG2IN
Kit for Rack UPS installation
FGCKITEVORT
UPS SINGLE-PHASE, POWER 2000 VA (C.FI 0,7) ON-LINE DOUBLE CONVERSION, SINGLE-PHASE IN/OUT, 220/230 V, 50/60 HZ, TRUE SINE WAVE, STABILIZATION ± 2%, AUTOMATIC/MANUAL BY-PASS, EPO (EMERGENCY POWER OFF), REMOTE ON/OFF, DRY CONTACT BOARD (OPTIONAL), SNMP INTERFACE (OPTIONAL), EXTENDED AUTONOMY (OPTIONAL), RJ45/RJ11, RS232, UPSILON 2000 SOFTWARE, 4 IEC TYPE OUTLETS, RACK 19"/TOWER POSITIONING (FOR A CORRECT INSTALLATION PLEASE USE MOUNTING KIT, NOT PROVIDED WITH THE UPS), HOT SWAP BATTERY, DIMENSIONS 44X13X48 CM (3U RACK), TOTAL WEIGHT 34 KG, AUTONOMY 16 MIN, 8 BATTERIES 12VDC 7.2AH (INSIDE UPS), UPS BATTERY RECHARGING CURRENT 1A MAX.
STANDARD WARRANTY: 24 MONTHS ELECTRONIC PARTS / 12 MONTHS BATTERY